Copper Conductor, Mica Tape Wrapped, XLPE Insulation, Individual & Overall Screen, LSOH Bedding, Galvanized Steel Wire Armoring, LSOH Sheath Instrumentation Cable

Our company specialized in Cable/Electrical Wire/ Conductor product

Copper Conductor, Mica Tape Wrapped, XLPE Insulation, Individual & Overall Screen, LSOH Bedding, Galvanized Steel Wire Armoring, LSOH Sheath Instrumentation Cable

type:Instrumentation Cable

standard:IEC/BS

size:0.5MM2-1.5MM2

construction:CU / MG / XLPE / IS / OS / LSOH / SWA / LSOH

rating voltage:300/500V

conductor material:Copper

conductor construction:Solid or Stranded

insulation material: XLPE

shield construction:Aluminum/polyester tape is applied over each pair metallic side down in contact with tinned copper drain wire, 0.5mm²

armor construction:Galvanized steel wire armor

sheath material:EPR (Ethylene propylene rubber)

specification or package can be produced as your request.

INQUIRY

Application
The armored fire resistant versions (Part 1 Type 2) are typically used in chemical and process industries where there is danger of fire. The galvanized steel wire armor provides excellent protection.

Construction
Conductor
Annealed or tinned copper, sizes: 0.5mm² and 0.75mm² multi-stranded(Class 5),
0.5 mm², 1.0 mm² solid(Class 1), 1.5mm² or 2.5mm², multi-stranded(Class 2) to BS6360
Insulation
Polyethylene insulation
Pairing
Two insulated conductors uniformly twisted together with a lay not exceeding 100mm
Individual screen
Aluminum/polyester tape is applied over each pair metallic side down in contact with tinned copper drain wire, 0.5mm²
Binder tape
Polyester tape
Collective screen
Aluminum/polyester tape is applied over the laid up pairs metallic side down in contact with tinned copper drain wire, 0.5mm²
Inner Sheath
LSOH(Low Smoke Zero Halogen) sheath
Amour
Galvanized steel wire armor
Outer sheath
LSOH(Low Smoke Zero Halogen) sheath Flame retardant to IEC60332-3-22 Fire resistant to IEC60331 Halogen free to IEC60754-1
Sheath color
Black or blue
Operating temperature:
-20˚C up to + 90˚C (fixed installation)
0˚C to +50˚C (during operation)
Minimum bending radius: 5 x OD

Conductor Area Size mm² 0.5 0.5 0.75 1 1.5
Conductor Stranding No. x mm 1 x 0.8  16 x 0.2  24 x 0.2  1 x 1.13 7 x 0.53
Conductor resistance max ohm/km 36.8 39.7 26.5 18.2 12.3
Insulation resistance min Gohm/km 5 5 5 5 5
Capacitance unbalance at 1 kHz(pair to pair screen) pF/250m 250 250 250 250 250
Max. Mutual Capacitance @ 1 kHz forNon OS or OS cables (except one-pair and two- pairs) pF/m 115 115 115 115 120
Max. Mutual Capacitance @ 1 kHz IS/OS cables (include 1 pair and 2 pair) pF/m 75 75 75 75 85
Max. L/R Ratio for adjacent cores(Inductance/ Resistance) μH/ohm 25 25 25 25 40
Test voltage Core to core V 1000 1000 1000 1000 1000
Test voltage Core to screen V 1000 1000 1000 1000 1000
Rated voltage max V 300/500 300/500 300/500 300/500 300/500
No.of Pairs No.and Dia. of Wires Nominal Conductor Cross- Sectional Area Nominal Thick- ness of Insulation Nominal Thick- ness of bedding Nominal Dia.   over Bedding Nominal Thick- ness of Armour Nominal Thick- ness of Sheath Nominal Dia. of Cable Approx. Weight
no./mm mm² mm mm mm mm mm mm kg/km
5 7/0.37 0.75 0.6 0.8 15 0.9 1.4 20.3 870
10 7/0.37 0.75 0.6 0.8 19.8 0.9 1.4 25.9 1480
5 7/0.44 1 0.6 0.8 14.8 0.9 1.4 20 890

The above data are approximate and subject to normal manufacturing tolerance.

Other types can be provided on specific request.

Packing:

On non-returnable wooden drums   or as customer request

Our Services:

1.Sufficient support for our tendering representatives.

2.OEM service available based on official & legal authorization.

3.Strict quality control system.

4.Faster lead time than our competitors.

5.Excellent quality with reasonable price.

6.Strong technical support (technical data, drawing, etc.)

7.Cable solutions to your particular requirements.

8.Free sample is available with economic express fee.

9.12 months quality guarantee after delivery.

INQUIRY

COPYRIGHT © 2017 Henan Province Xinchang Copper Co.,Ltd.